Voltage Drop Calculator

Voltage drop in a cable and the right wire size

Calculate the voltage drop along a copper or aluminium cable for a load, check it against the 3% or 5% limit, and find the smallest cable size that keeps within it.
Share
Try an example:
A
m
%
Your result will appear here as you type.

About Voltage Drop Calculator

Formula

Vd = 2 × L × I × ρ ÷ A (single-phase)

Worked examples

16 A over 20 m of 2.5 mm² copper

2 × 20 × 16 × 0.0172 ÷ 2.5 = 4.4 V, or 1.91% of 230 V - within 3%.

How it works

  1. Single-phase: Vd = 2 × length × current × resistivity ÷ cross-section.
  2. Three-phase: the factor 2 becomes √3.
  3. Copper resistivity 0.0172 and aluminium 0.0282 Ω·mm²/m at 20 °C.

What you need

  • Current, one-way cable length and cable size.

Tips

  • Long runs to a water pump or outbuilding often need a size larger than the current alone suggests.

Limitations

  • Electrical work must be done by a licensed electrician - use these figures for planning only.
  • Uses resistance at 20 °C; hot cables have slightly higher drop. Does not check current rating.

Runs in your browser. Calculations run in your browser - nothing you enter is sent anywhere.

Definitions

Voltage drop
Voltage lost along a cable because of its resistance.

Frequently asked questions

What voltage drop is acceptable?+

Commonly 3% for lighting circuits and 5% for others, measured from the supply to the furthest point.